D400-18-00 1 I56-494-13R
PRINTED IN MEXICO
6424 Projected Beam Type
Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Specifications
General
Range: 30 to 330 Feet (9.1 to 100.6 m)
Sensitivity: 30% ±5% Total Obscuration, or
55% ±5% Total Obscuration
Spacing: 30 to 60 Feet (9.1 to 18.3 m)
Response Time: Alarm: 15 Seconds Max.
Trouble: 15 Seconds Max.
Trouble Condition: 95% or More Obscuration
Improper Initial Alignment
Self-compensation limit reached (service needed)
Test/Reset Features: Obscuration Filters (ALARM/NO ALARM)
Local Alarm Reset Switch
Remote Test and Reset Switch Capability
(compatible with RTS451 Test Station with Magnet)
Indicators: Alarm: Remote Output, Local LED (red)
Trouble: Remote Output, Local LED (yellow)
Normal Operation: Local LED (flashing green)
Alignment Aid: LED Bar Graph (4 red LEDs)
Relays: Alarm; Trouble
Environmental
Temperature: –22°F to 131°F (–30°C to 55°C)
Humidity: 10% to 93% RH Noncondensing
Mechanical
Weight: Receiver: 1.5 lbs (680 g)
Transmitter: 1.3 lbs (590 g)
Mounting: Ceiling or Wall, Separate Mounting Brackets Provided
Wiring: Plug with Attached Cable
Adjustment Angle: Ceiling: ±30° Horizontal/60° Vertical
Wall: ±90° Horizontal/60° Vertical
Electrical (Receiver)
Voltage: 20 to 32 VDC
Maximum Ripple Voltage: 6.0 volts (Peak-to-peak)
Current (24 VDC): Avg. Standby: 10mA Max.
Avg. Alarm: 28.4mA Max.
Avg. Trouble: 27.1mA Max.
Start-up Surge: 19mA Max.
Relay Contacts: .5A at 30 VAC/DC
Reset Time: .6 Seconds Max.
Start-up Time (after 5 min. reset): 1 Minute Maximum
Power Loss: Retain Memory for 5 Minute Minimum
Electrical (Transmitter)
Voltage: 18.8 to 32 VDC
Maximum Ripple Voltage: 5.6 volts (Peak-to-Peak)
Avg. Current (24 VDC): 10mA Max.
Vedere la pagina 0
1 2 3 4 5 6 ... 11 12

Sommario

Pagina 1 - Smoke Detector

D400-18-00 1 I56-494-13RPRINTED IN MEXICO6424 Projected Beam Type Smoke DetectorINSTALLATION AND MAINTENANCE INSTRUCTIONS 3825 Ohio Avenue, St. C

Pagina 2 - D400-18-00 2 I56-494-13R

indicate alignment mode, but the trouble relay will not activate. If the receiver is left in the alignment mode for more than an

Pagina 3 - D400-18-00 3 I56-494-13R

NOTE: Before testing the detector, check for the presence of the flashing green LED at the receiver, making sure not to disturb or block the beam

Pagina 4 - D400-18-00 4 I56-494-13R

D400-18-00 12 I56-494-13R ©2004 System Sensor PRINTED IN MEXICOThree-Year Limited WarrantySystem Sensor warrants its enclosed smoke dete

Pagina 5 - D400-18-00 5 I56-494-13R

Before InstallingPlease thoroughly read this manual and applicable sections of System Sensor’s Projected Beam Detector Application Guide. Copie

Pagina 6 - D400-18-00 6 I56-494-13R

In a room with a smooth ceiling, detectors should be spaced between 30 and 60 feet. One-half that spacing between the beam and the sidewall may be use

Pagina 7 - D400-18-00 7 I56-494-13R

Mounting BracketsInstall a ceiling or wall bracket for both the receiver and transmitter so that when mounted, the receiver and the t

Pagina 8 - 6 CONDUCTOR

CLASS ARETURN LOOPINITIATINGLOOPPOWERTODETECTORSLISTED PANELTRANSMITTERBLUE GREENORANGEGREENBLACKRED-WHITESTRIPEWHITEWHITE-BLACKSTRIPEGRAYVIOLETWHITE-

Pagina 9 - D400-18-00 9 I56-494-13R

aid. If the remote power configuration is used, the remote power source must comply with all codes and directives of the Authority Having Juri

Pagina 10 - PRINTED IN MEXICO

Figure 12. Wall mounting:HORIZONTAL ADJUSTMENT SCREW(#10-24 x 1-3/8 in.)METAL WASHERMOUNTING HUBMOUNTING HUBALIGNMENTLEDsSTATUSLEDs(RECEIVER ONLY)BEAM

Pagina 11 - D400-18-00 11 I56-494-13R

Figure 14. Rear view receiver:ACCESS DOORCONNECTOR16 CONDUCTORCABLERESET SWITCH3055SENSITIVITYSELECT SWITCHNAALIGNMENTMODE SWITCHC0548-00Figure 15.

Pagina 12

4 RED LEDs USEDFOR ALIGNMENTGREEN: FLASHES APPROXIMATELY EVERY2 SECONDS IF POWERED UP ANDSENSING A SAFE CONDITION.YELLOW: TURNS ON WHILE A TROUBLECON

Commenti su questo manuale

Nessun commento